EPSx514-1
MTL4514 – MTL5514SWITCH/PROXIMITY- DETECTOR INTERFACE
MTL4514
Hazardous areaTo earth-leakagedetector *654+Safe areasingle channel with line fault detection and phase reversal
680WTo earth-leakageLFDdetector *121110987LFDThe MTLx514 enables a safe–area load to be controlled, through a relay, by a proximity detector or switch located in a hazardous area. Line faults are signalled through a separate relay and indicated on the top of the module. Switches are provided to select phase reversal and to enable the line fault detection.
22kWSwitch-type sensorsrequire resistorsif LFD is selected321Output131420 to 35V dcVs+VsSPECIFICATION
See also common specification
Number of channels
One
Location of switch
Zone 0, IIC, T6 hazardous areaDiv.1, Group A, hazardous locationLocation of proximity detector
Zone 0, IIC, T4–6 hazardous area, if suitably certifiedDiv.1, Group A, hazardous locationHazardous–area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (> 10kΩ in input circuit)Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are indicated by an LED. Line fault relay is energised and channel output relay de-energised if input line-fault detectedOpen-circuit alarm on if Iin < 50µAOpen-circuit alarm off if Iin > 250µAShort-circuit alarm on if Rin < 100ΩShort-circuit alarm off if Rin > 360Ω
MTL5514
Hazardous areaTo earth-leakagedetector *654+Safe areaLFD680W22kWSwitch-type sensorsrequire resistorsif LFD is selected71011121314LFD321OutputVsVs+20 to 35V dc*Signal plug HAZ1-3 is required for access to this functionLED indicators
Green: power indication
Yellow: channel status, on when output energisedRed: LFD indication, on when line fault detectedMaximum current consumption
25mA at 24V dc
Power dissipation within unit
0.6W at 24VSafety description
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dcSIL capable
These models have been assessed for use in IEC 61508 functional safety applications. See data on MTL web site.
Note: Resistors must be fitted when using the LFD facility with a contact input500Ω to 1kΩ in series with switch20kΩ to 25kΩ in parallel with switch
Safe-area output
Channel: Single pole relay with changeover contactsLFD: Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
MTL4514
Response time:Contact rating:
10ms maximum10W, 0.5A,
35V dc
MTL5514
10ms maximum
250V ac, 2A, cosØ >0.7,40V dc, 2A, resistive load
The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283AMERICAS Tel: +1 281 571 8065 Fax: +1 281 571 8069ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Oct 2009